Cecomp Electronics, API 4008 G, Potentiometer to DC Isolated Signal Conditioner, 18 Field Configurable Output

Features:

  • Accepts Wide Range of Potentiometers
  • Set-up via External Rotary Switches
  • Easy-to-use Setup Tables
  • Selectable Voltage or Current Outputs
  • 2000 VRMS Isolation Input/Output/Power
  • Input and Output LoopTracker® LEDs
  • Functional Test Button

Applications:

  • Over, Under, Out-of-Range Position Monitoring
  • Remote Control of Positioning Devices
  • Simplify Control of Potentiometer Outputs

The API 4008 G accepts a resistance input from potentiometer, slidewire, linear position, displacement, or rotational devices and provides an optically isolated DC voltage or current output that is linearly related to the potentiometer position.

The API 4008 G will accept any potentiometer with a value of 0-100 Ω through 0-1 MΩ without recalibration and without affecting accuracy as long as 100% of the potentiometer range is used.

The API 4008 G output can be field-configured via external rotary and slide switches. 10 DC voltage or 8 DC current ranges can be selected from the table on the module.

The full 3-way (input, output, power) isolation makes this module useful for ground loop elimination, common mode signal rejection or noise pickup reduction.

Output Loop Power Supply

The API 4008 G has an 20 VDC loop excitation supply for the output. This power supply can be used to power a passive mA device.

LoopTracker

API exclusive features include two LoopTracker LEDs (green for input, red for output) that vary in intensity with changes in the process input and output signals. These provide a quick visual picture of your process loop at all times and can greatly aid in saving time during initial startup and/or troubleshooting.

Output Test

An API exclusive feature includes the test button to provide a fixed output (independent of the input) when held depressed. The test output level is potentiometer adjustable from 0 to 100% of output span. The output test button greatly aids in saving time during initial startup and/or troubleshooting.

Specifications Table:

Potentiometer Input Ranges Full travel of potentiometer and 3 wire connection required

  • Minimum: 0-100 Ω
  • Maximum: 0-1 MΩ

Consult factory for other ranges and configurations

Input Impedance 10 MΩ minimum
Common Mode Rejection 100 dB minimum
DC Output Range Field selectable ranges via switch settings

  • Voltage: 0-1 VDC to 0-10 VDC, 10 mA max
  • Bipolar voltage: ±5 VDC or ±10 VDC
  • Current: 0-2 mADC to 0-20 mADC, 20 V compliance, 1000 Ω at 20 mA
Output Logic Normal acting (standard). Reverse acting by reversing potentiometer wires
Calibration Multi-turn zero and span potentiometers for output (±15% of span adjustment range typical)
Output Loop Power Supply 20 VDC nominal, regulated, 25 mADC, max. ripple <10 mVRMS
Output Test Potentiometer adjustable 0-100% of span
Output Ripple and Noise Less than 10 mVRMS
Linearity Better than ±0.1% of span
Ambient Temperature Range and Stability
  • -10°C to +60°C operating ambient
  • Better than ±0.02% of span per °C stability, calculated, not tested
Response Time 70 milliseconds typical
Isolation
  • 2000 VRMS minimum
  • Full isolation: power to input, power to output, input to output
Installation Environment
  • IP 40, requires installation in panel or enclosure
  • Use with API 008 or API 008 FS socket
  • Socket mounts to 35 mm DIN rail or can be surface mounted UL 508C pollution degree 2 environments or better
Power 115 VAC ±10%, 50/60 Hz, 2.5 W max.